Expert opinion from Hervé Miler, Project Manager for Airflow and Thermal Engineering at CETIAT.
Air quality in industrial settings is a key concern, both for safeguarding the health of workers and ensuring the quality of the manufactured product. In areas with specific pollution, where dust, mists or various gaseous emissions are produced, solutions for vapour suppression, source capture or even general ventilation must be implemented to ensure that pollutant concentrations remain well below the authorised Exposure Limit Values. The issue is all the more critical as it has a direct impact on energy consumption.
However, these issues are not always fully understood. Unlike water, air is invisible and more difficult to grasp, making it harder to understand airflow patterns or detect leaks. The scarcity of practical training courses directly dedicated to ventilation and IAQ issues undoubtedly makes the task even more complex. Consequently, potential malfunctions are sometimes only detected over the long term, and indirectly, through the emergence of health issues among operators, variations in product quality, or rising energy costs.At the same time, it is quite logical to note that air handling checks on installations are often minimal. The legal obligation to record the original performance and any changes in a logbook (“The Installation File”) is little known and therefore rarely applied. In a sense, operators are sometimes more at the mercy of the systems than they are in control of them, and are often at a loss when faced with such deviations or new problems that arise. However, simple advice can be provided to support manufacturers in managing IAQ and energy consumption.
#1 – Questioning whether it is absolutely necessary to emit pollutants
Whilst it may seem unrealistic, this first point is nonetheless crucial and often overlooked. Implementing radical yet cost-effective changes to production methods or equipment is a direct contributor to improving indoor air quality. For example, priority should be given to the use of electric-powered handling vehicles (whether autonomous or not) rather than vehicles with internal combustion engines. This means fewer sources of pollution to deal with in a workshop. Another example is more controlled combustion in furnaces, or the use of alternative cutting fluids in machining operations; these are powerful measures for reducing pollutants potentially emitted into the working environment or for reducing air consumption.
#2 – Capturing the pollutant at source rather than treating it by dilution: a factor of 1 to 50 in terms of energy consumption
Capturing pollutant emissions at source improves indoor air quality (IAQ) and reduces energy costs accordingly, as it requires lower airflow rates. It is therefore a ‘win-win’ approach: the air is healthier, and the airflow rates required are lower. Conversely, reducing pollutant concentrations through dilution in a general ventilation system is less effective in terms of IAQ and systematically requires higher air flow rates. Consequently, heating or cooling costs, which are directly proportional to circulating air flow rates, are effectively reduced.
It is in fact regularly observed that the flow rates required for a source capture solution are often up to 50 times lower than those for a general ventilation dilution solution. Energy costs, during heating or cooling periods, follow the same ratio and, consequently, the potential for savings is of a similar order. This reduction in operating costs justifies the investment required to modify or adapt existing ventilation systems.
#3 – An air distribution system is not an electrical system
It is often the case that, due to a lack of understanding of ventilation systems, misjudgements can hinder the system’s efficiency. For example, an additional ventilation component—whether passive (duct, filter, etc.) or active (fan, chimney, etc.)—connected without prior consideration to an existing ventilation system will potentially disrupt the balance and performance of the whole system. This will result in reduced ventilation efficiency and compromise indoor air quality in the workplace.
Any modification to the ventilation system must therefore always be assessed in advance. A common mistake is to assume that an air distribution system follows the same rules as a domestic electrical system, and that one can, as it were, ‘connect’ a new component without affecting the existing system, much like plugging an additional domestic appliance into a power strip.
#4 – Network maintenance: watch out for dirt build-up and electrical connections
Maintenance of the ventilation system is also essential and should be carried out at least once a year. This includes cleaning the ventilation ducts but also, and perhaps most importantly, maintaining the fan, whether that involves the propeller shaft or the blades. Indeed, deposits on the fan blades, much like ice on an aeroplane wing, can only degrade their aerodynamic profile and thus the resulting velocity profiles. The airflow produced is therefore inevitably lower (although the actual impact depends on the operating point of the system and the fan). Inadequate cleaning of the fan is thus the main cause of reduced performance in around 10% of ventilation issues.
Furthermore, it is not uncommon to find that fans have been wired in reverse. This is, unfortunately, a common mistake on a terminal block or in an electrical cabinet, and is the main cause of failure in around 20% of cases. It is not immediately obvious, particularly in the case of centrifugal fans, where a reversed rotation of the impeller does not alter the direction of air flow. Thus, in the case of an extraction system, for example, the suction is still felt, but with actual flow rates that may be 10 to 50 times lower than the expected values, resulting in a reduced indoor air quality in the workshop.
#5 – Suction is not the reverse of blowing
When analysing an extraction system, it is important to understand that the source of the extracted air is not unidirectional but, on the contrary, multidirectional. The air flow lines leading to the extraction point thus originate from the entire immediate space. The air extracted is therefore not only stale air, but also air from neighbouring unpolluted areas, drawn in by the negative pressure generated.
Thus, isovelocity and isopressure surfaces resemble topologies that are often cylindrical or spherical, but rarely rectilinear (except in specific cases such as fume cupboards or extraction booths). In other words, an extraction system cannot be ‘ballistic’ or have a ‘range’. An extraction system is therefore not a “reverse” blow-off system. This multidirectional aspect is essential in calculating the required flow rates and in the general understanding of extraction phenomena and capture efficiency.
To develop their expertise in the field of air quality, manufacturers can contact independent organisations (such as INRS, ADEME, CETIAT, etc.) that offer research or training. Specialists are on hand to share their knowledge or offer advice. Their remit includes diagnosing, explaining and supporting manufacturers with their IAQ and energy consumption issues.